beplay888官网

用加热的压板过热

Click on image to enlarge

图1A small heated platen press for an aerospace parts manufacturer would close and hold pressure for 1 to 3 hours based on the part being molded. When the system was first installed, it developed trouble with the oil overheating. The employees made a design change, installing a 5-psi check in the pump case drain line back to tank and a ½-psi check going to the main return line. (See the circuit showing the final design.)

This modification worked just fine. When the press was in the clamped mode, the case drain would pass through the filter and heat exchanger, cooling the pump case drain during the holding phase. If the cylinder was cycled, it would cause flow and some back pressure in the main tank line and the back pressure would hold the ½-psi check closed, causing the pump case flow to divert directly to the tank over the 5-psi check. A 5-psi check was used since the shaft seal of the pump was limited to 10 psi.

Every so often, the press would start overheating during the clamped cycle. The employees would lower the pressure setting on the safety relief to flush any contamination that may cause it to leak and reset it back to 3000 psi. They would change the filter element, which looked dirty, and check the water connections on the heat exchanger for flow or corrosion.

什么可能导致问题,解决方案是什么?

See the Solution

When pressure-compensated pumps idle for long periods of time, the case flow can cause the reservoir oil to overheat. Using a 5 and ½ psi check valve circuit allowed the case flow to be cooled when the main system is static and the pump is compensated. When the designer installed the modification to cool the case drain, he should have connected the outlet of the ½-psi check to only flow through the cooler and not the 3-micron filter. The 15-gpm filter was undersized to begin with since the return flow from the cylinder retracting was 24½ gpm. As the dirt and contaminants accumulated in the filter, the pressure drop increased. As soon as the pressure drop exceeded 4½ psi, the case drain flow was returning to the reservoir through the 5-psi check heating up the oil.

由Robert Sheaf,CFPAI/AJPP,CFPE,CFP,CFPEC,CFPMT,CFPMIP,CFPMIP,CFPMMH,CFPMIH,CFPMH,CFPMM,CFC工业培训

Share this information.

相关的帖子

3 thoughts on “Overheating of Press with Heated Platen”

  1. Jesse Lucking 说:

    My first thought is that the pump compensator and main relief probably weren’t/aren’t set properly and there’s interaction between them causing full pump flow to intermittently flow over the relief. Especially since they are periodically “flushing” the relief by lowering the pressure and resetting it.

    Another possibility is that because during the clamped phase (assuming compensator is working correctly) the only flow would be case leakage and whatever is needed to maintain pressure. Assuming the reservoir is sized adequately there may not be enough cooling capacity. A separate cooling loop could be added just to constantly circulate reservoir oil through the heat exchanger and also flush the pump case.

  2. Grant Green 说:

    在液压电路设计中不做什么的好教训…

    过热是由于允许案例流动两个可能引起的。您希望它能通过过滤器和冷却器,但是一旦这条路径超过5 psi,它就不会,当这种情况发生时,当泵试图保持夹紧压力时,您就会失去系统中的所有冷却。
    滤波器的压力下降是可变的,并且随着元素加载污染物的负载而增加。同样,使用冷却器,但随着油的变暖,这将减少。
    Call it the ‘hydraulic hope’ design cooling approach. Never a real good idea to install check valves in a case drain line especially when other components downstream components have variable pressure drops.

    To fix this circuit properly. First off get rid of the pump with control that doesn’t do what you want it to do. Get a pump with a remote compensator control. Get rid of the check valves on the case drain lines. Also

    Heated press clamping a piece for several hours is a perfect spot to apply an accumulator (downstream of PO check valves) and you must also put in a thermal relief valve on the cap side of the cylinder (presumably the clamp cylinder is clamping). A pressure switch installed on the cap side of the cylinder cycles the electric motor on/off if required and the accumulator maintains the clamping pressure for hours. The power unit is off probably 90% of the time during the clamping/mold process. That is the end of your overheating problem.

    Add in also an accumulator bleed-down safety valve for maintenance. If you want to be an all in ‘keener’ also add a kidney loop fixed displacement pump and use it for filtration and cooling added on to thru drive of the new pump with remote compensator control.

  3. 吉姆·法里尔(Jim Farrior) 说:

    我同意这两个解决方案。我的第一个想法是使用带有kepner o-leak po交叉检查和压力开关的开放中心线轴来控制用于固定的累加器。这样,所有流量都流向过滤器,并在低压下冷却。我也同意您的“液压希望”想法。我喜欢那个评论。当泵的补偿设置未明确设置并且您有2条路径可以走时,您只是不确定发生了什么。

    吉姆·法里尔(Jim Farrior)

发表评论

Your email address will not be published.Required fields are marked*

Baidu